Published date: 3 October 2022

Closed opportunity - This means that the contract is currently closed. The buying department may be considering suppliers that have already applied, or no suitable offers were made.


Closing: 17 October 2022, 12pm

Contract summary

Industry

  • Gas-detection apparatus - 38431100

Location of contract

M5 4WT

Value of contract

£70,000

Procurement reference

UoS/ST/22/23/QTR1/Gas Detection System

Published date

3 October 2022

Closing date

17 October 2022

Closing time

12pm

Contract start date

7 November 2022

Contract end date

17 April 2023

Contract type

Supply contract

Procedure type

Open procedure (below threshold)

Any interested supplier may submit a tender in response to an opportunity notice.

This procedure can be used for procurements below the relevant contract value threshold.

Contract is suitable for SMEs?

Yes

Contract is suitable for VCSEs?

No


Description

The University is looking to update our gas detection system in our Cockcroft building. A gas detection survey has been completed.

- install Solenoids on the working gases within nine laboratories to allow each area to be isolated individually if the / when unsafe levels of gas are sensed and / or when the oxygen within air has been depleted. Each solenoid / bank of solenoids will require a 13amp unswitched fuse spur.
- A Gas Detection System that will monitor Carbon Dioxide, Flammable Gases and Oxygen Depletion within all labs
- Install of a main Gas Detection panel in the building foyer. The control panel will provide audible and visual indication of the sensors that are located within each Lab, this will also have volt free contact for the BMS system
- Status Room Indicators / Beacon Sounders will be located at the Entrance/Exits to the working areas and with the Laboratory areas, which will be linked into to the Solenoid. The Room Status Indicator / Beacon Sounders will alert the users as to when unsafe levels of gas are sensed and / or when the oxygen within air has been depleted.
- The Gas Detection will consist of the following items per floor / room:- • Building Gas Detection Panel • Room Indicator • Oxygen Depletion Sensors • Carbon Dioxide Sensors • Flammable Sensors • Surface Mounted Conduits • Installation • Commission • Demonstration
- All pipework will be degreased copper to BS EN 13348 table x R250 with joints brazed using a fluxless jointing technique and utilising an inert gas shield, pipelines will be identified as appropriate.
- All pipework will be 316 Stainless Steel, with all joints twin ferrule type, pipelines will be identified as appropriate.
- The above installation and all associated ancillaries will be installed to N.5 Purity (99.999%) unless stated otherwise.
- Upon completion the installation will be subject to a pressure test and commissioned, all appropriate certification will be issued.
- All works will be carried out in accordance with BCGA codes of practice.
- The Contractor is to provide a programme a draft programme of works as part of the tender return
- On completion of each installation the necessary tests must be carried out and test certificates prepared and recorded.
- Install of an IGD system.

The Mechanical and Electrical installations shall comply with the following:

- CIBSE Design Codes Technical Memoranda and Commissioning Codes
- BS 7671: IEE Wiring Regulations (current version)
- The Health and Safety at Work Act
- The Local Authority's Bye-Laws and Safety Regulations
- The Local Authority's Building Control Requirements
- Any other special Licensing Authority's requirements and Safety Regulations
- All appropriate current British Standards and Codes of Practice

For full tender information and to express an interest please visit our InTend portal via: https://in-tendhost.co.uk/salford/aspx/Home.